Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM00382
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2006 | FRAMING | Approved | IVRS - Inspection :* | |
05/17/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO COVER ALL EXCEPT WALLS CONTAINING DWV TEST/NETTING ONLY 2) WAITING FOR CITIES APPROVAL ON 9/D1 |
|
05/15/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY SUPER 2) STAPLE UNDER SOUTH EAST WINDOW |
|
05/11/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
05/04/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BADLY WRAPPED STUD AT SOUTH WALL ON SE CORNER. 2. ALTERNATE DETAIL FOR 9 ON D-1 NOT SUPPLIED. 3. COMPLETE TOP 3 SOUTH WALL OF SW CORNER. 4. UNABLE TO LOCATE INFO ON WINDOWS. 5. ISLAND ELECTRIC SUPPLY DOES NOT COME UP IN WALL. 6. NAIL STOP WASHER DRAIN AT BOTTOM PLATE. 7. NAIL PROTECT FRESH AIR DUCT AT FURNACE PLATFORM. 8. CONNECT EXHAUST FLEX TO FAN IN TOILET ROOM. 9. GROUND WIRE FOR CABLE/SATELLITE SYSTEM MUST GO TO MAIN ENTRANCE SERVICE, NOT TO BEDROOM RECEPTACLE. |