Permit: T06CM00382

Parcel: 141091640


Addresses:

7947 S TALACO TR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM00382

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/11/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATHE NOT STAPLED TO ALL STUDS
2) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICES
3) NO TRUSS DRAWINGS ON SITE
4) NO DWV WATER TEST
5) FIRE BLOCK THROUGHOUT
6) EXTERIOR CLIP NOT APPROVED. PROVIDE ENGINEERING REPAIR
7) PROVIDE APPROVED DETAIL FOR SHEAR TRANSFER AT INTERSECTING WALLS
8) FIRE BLOCK REQURES TWO LAYERS OF 1/2" OSB
9) STOPPED INSPECTION-TO MANY ITEMS
04/19/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
N/R AS PER SUPER
04/14/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) H1D AND H1A TRUSSES MISSING BRACES
2) PROVIDE APPROVED DETAIL FOR STUBBED TRUSS BEARING IN PLACE OF 9/D-1