Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* AFTER HOURS INSP. SAT. 5:30 AM |
|
| 03/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PICTURE #1 -- SUPPORT OR CONDUIT CANNOT BE ATTACHED TO EXISTING CEILING SUPPORT WIRES MUST BE INDEPENDENT. PICTURE #2 -- J-BOX OVERFILLED AND COVER MISSING PICTURE #3 -- J-BOX NEEDS TO BE GROUNDED AND LOWERED PICTURE #4 -- EXISTING CONDUITS CANNOT BE USED TO SUPPORT NEW ONES PICTURE #5 -- J-BOX OVERFILLED WITH CONDUCTORS, OPENING IN BOX NEEDS TO BE SEALED. PICTURE #6 -- AGAIN CONDUIT CANNOT BE SUPPORTED BY CONDUIT. PICTURE #7 -- CONDUITS TO BE SUPPORTED WITHIN 3' OF J-BOXES PICTURE #8 -- J-BOX ONLY SUPPORTED BY CONDUIT, NEEDS OWN SUPPORT. PICTURE #9 -- J-BOX NEEDS TO BE GROUNDED AND COVER INSTALLED. PICTURE #10 -- CONDUIT SUPPORT REQUIRED WITHIN 3' OF BOX PICTURE #11 -- SAME AS PICTURE #10 PICTURE #12 -- COVER MISSING ON J-BOX, PROVIDE PROPER SUPPORT OR CONDUITS. |
|
| 03/10/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. I NEED TO HAVE ACCESS TO CEILING FOR THE INSPECTION, HOWEVER DUE TO ASBESTOS, CEILING CAN'T BE OPENED. I AM NOT CERTIFIED FOR WORKING/INSPECTION OF AREAS WITH ASBESTOS. |