Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
AFTER HOURS INSP. SAT. 5:30 AM
03/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PICTURE #1 -- SUPPORT OR CONDUIT CANNOT BE ATTACHED TO EXISTING CEILING SUPPORT WIRES MUST BE INDEPENDENT.
PICTURE #2 -- J-BOX OVERFILLED AND COVER MISSING
PICTURE #3 -- J-BOX NEEDS TO BE GROUNDED AND LOWERED
PICTURE #4 -- EXISTING CONDUITS CANNOT BE USED TO SUPPORT NEW ONES
PICTURE #5 -- J-BOX OVERFILLED WITH CONDUCTORS, OPENING IN BOX NEEDS TO BE SEALED.
PICTURE #6 -- AGAIN CONDUIT CANNOT BE SUPPORTED BY CONDUIT.
PICTURE #7 -- CONDUITS TO BE SUPPORTED WITHIN 3' OF J-BOXES
PICTURE #8 -- J-BOX ONLY SUPPORTED BY CONDUIT, NEEDS OWN SUPPORT.
PICTURE #9 -- J-BOX NEEDS TO BE GROUNDED AND COVER INSTALLED.
PICTURE #10 -- CONDUIT SUPPORT REQUIRED WITHIN 3' OF BOX
PICTURE #11 -- SAME AS PICTURE #10
PICTURE #12 -- COVER MISSING ON J-BOX, PROVIDE PROPER SUPPORT OR CONDUITS.
03/10/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. I NEED TO HAVE ACCESS TO CEILING FOR THE INSPECTION, HOWEVER DUE TO ASBESTOS, CEILING CAN'T BE OPENED. I AM NOT CERTIFIED FOR WORKING/INSPECTION OF AREAS WITH ASBESTOS.