Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL 1. USE TERMINAL ENDS WITH STRANDED CONDUCTORS AT DEVICES. |
|
| 07/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT CONDUIT ALONG SIDE OF PANEL AND TIGHTEN LOOSE FITTINGS. 2. TIGHTEN ALL LOOSE FITTINGS 3. GROUND JUNCTION BOXES 4. FILL UNUSED OPENINGS IN BOXES 5. REJECTION PINS NEEDED FOR FUSES 6. PLANS CALL FOR PURCELC CABINET TO HAVE 125A BREAKER WE HAVE 100A 7. UNIT IS OPERATIONAL WITH A GENERATOR WITHOUT CLEARANCES. |