Permit: T06CM00371

Parcel: 13329001A


Addresses:

545 N CAMINO SECO

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
1. USE TERMINAL ENDS WITH STRANDED CONDUCTORS AT DEVICES.
07/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT CONDUIT ALONG SIDE OF PANEL AND TIGHTEN LOOSE FITTINGS.
2. TIGHTEN ALL LOOSE FITTINGS
3. GROUND JUNCTION BOXES
4. FILL UNUSED OPENINGS IN BOXES
5. REJECTION PINS NEEDED FOR FUSES
6. PLANS CALL FOR PURCELC CABINET TO HAVE 125A BREAKER WE HAVE 100A
7. UNIT IS OPERATIONAL WITH A GENERATOR WITHOUT CLEARANCES.