Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/12/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C DISCONNECT AND ELECTRIC PANEL SHALL NOT BE OVER A/C |
|
| 07/11/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 10 NOT READY PER BEN |
|
| 07/10/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ARC FAULT ON BEDROOM CIRCUITS 2) PROVIDE 20 AMP FUSES PER SPECS ON A/C UNIT 3) RE-IDENTIFY WHITE WIRE AT A/C SUB PANEL BEING USED AS A UNGROUNDED CONDUCTOR 4) PROVIDE GFCI PROTECTION AT RECEPTACLE BATHROOM COUNTER |