Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MUST RUN A MAIN BONDING JUMPER FROM UFER TERMINATION TO NEUTRAL BAR 2. REMOVE GREEN SCREW FROM NEUTRAL IN SUB-PANEL |