Permit: T06CM00332

Parcel: 20914001C

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T06CM00332

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2007 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
11/15/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
11/08/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TEST ON ALL ROUGH SOIL PIPING ON UNITS #2 THRU #8
2) PROVIDE 1/4" PER FOOT FALL ON ALL 3" PIPING AT BUILDING DRAIN TO SEWER
3) PROVIDE 1/8" PER FOOT FALL ON ALL 4" PIPING
4) PROVIDE TRACER WIRE ON ALL ABS UNDERGROUND PIPING
09/06/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
09/01/2006 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
07/25/2006 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE MINIMUM 1/4" PER FOOT FALL OF 3" PIPING AT BUILDING DRAIN TO SEWER CONNECTION.
2. SHADE PIPING CORRECTLY.