Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/26/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER OFFICE (H. LEYVA) |
|
| 09/21/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) REPAIR AND SEAL STUCCO AT MECHANICAL PENETRATIONS 2) FILL DWV 3) NAIL OFF FHA STRAPS, AT STAIRS 4) REPAIR LINE SET INSULATION |
|
| 09/14/2006 | FRAMING | Cancelled | IVRS - RI canceled | |
| 09/01/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT READY WITH ITEMS BELOW B-VENT MISSING FOR W/H SUPPORT TRAP FOR 2ND FLOOR TUB |
|
| 08/29/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VACUUM BREAK REQUIRED AT HOSE BIB 2) SEAL LATHE AT SMART BOX AND ALL PENETRATIONS 3) FILL DWV 4) FIRE STOP IN GARAGE AT ENTRY POP-OUT 5) FIRE STOP 2ND FLOOR PEN. 6) WIRE CUT AT KITCHEN HALF-WALL 7) RPS STRAP REQUIRED AT OVER NOTCHED PLATE UNDER STAIRS 8) INSUFFICIENT NAILS IN STRAP AT TOP OF STAIRS 9) FIRE STOP AT SUPPLY DUCT THROUGH FLOOR 10) FIRE STOP GARAGE ATTIC IN 2ND FLOOR BATH 11) FIRE STOP 2ND FLOOR CHASE S.W. CORNER 12) A/C COPPER INSULATION DAMAGED OVER STAIRS 13) COMPLETE MECH BLOCKING |