Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BANG PLATE REQUIRED AT DRYER VENT 2) SECURE B-VENT AT 2ND FLOOR AND MAINTAIN CLEARANCE TO COMB. |
|
| 06/23/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING MECH 2) APPROVED TO INSULATE 3) COMPLETE WORK |
|
| 06/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 3, 4, 5 AND 7 FROM 6/9/06 INSPECTION 2) SECURE 4 GANG SWITCH BOX 2ND FLOOR 3) IMPROVE WORKMANSHIP OF B-VENT INSTALLATION OVER FURNACE-2ND FLOOR 4) NAILS MISSING IN GIRDER HANGERS-2ND FLOOR FRONT BEDROOM 5) SEAL VAPOR BARRRIER-2ND FLOOR |
|
| 06/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE PREVIOUS LIST 2) REPLACE VANDALIZED WIRES THROUGHOUT 3) STOPPED INSPECTION |
|
| 06/09/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FHA STRAP TOP PLATES AT GAS MAIN RISER FOR OVER BORE. 2. BANG PLATE WIRES AT GARAGE FRONT + KIT. E. WALL 3. NEED 1" CLEARANCE TO "B" VENT & FIREBLOCK SAME 4. CORRECT OVERRUN OF DRYER DUCT 5. NEED DWV TEST 6. SHIM HEADERS WHERE NEEDED 7. SECURE THERMO WIRE - 1ST. FL. BED 8. BLOCK DUCT BOOT - 1ST. FL. BED 9. CORRECT MASTER LAV STUD OVERBORES AT GIRDER TRUSS. 10. NEED POST UNDER GIRDER TRUSS OVER ENTRY DOOR. 11. STOPPED INSPECTION |