Permit: T06CM00315

Parcel: 140295870

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/26/2006 BUILDING - FINAL Approved IVRS - Inspection :*
07/24/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPEAT ITEMS
2) REFEE WILL APPLY
07/20/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL GARAGE CEILING AND TAPE GARAGE WALL AT WATER HTR
2) REMOVE GFCI STICKERS ON RECEPTACLES NOT GFCI PROTECTED
3) REPAIR/REPLACE SMOKIE IN BED 2
4) OUTLET IN L.R. CAN NOT SHARE SMALL APPLIANCE CIRCUIT
5) KITCHEN HOOD VENT GROUNDED INCORRECTLY
6) CONDUCTORS NOT PROTECTED AT HOOD VENT
7) MECH NOT PER PLAN 8 X 8 AND 10 X 10 REQUIRED IN L.R.
8) SINGLE WALL VENTING MUST BE USED INSIDE FURNACE CASING
9) GAS TO FURNACE NOT CONNECTED
10) STOPPED INSPECTION
07/18/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER