Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM00306
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
04/03/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED REVISED PLAN SO FLOOR PLAN MATCHES EXISTING (WALLS @ STORAGE & OFFICE AREAS) |
|
03/30/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED APPROVALS FROM ALL OTHER TRADE INSPECTORS. 2. VERTICAL GRAB BARS @ RESTROOM INSTALLED TOO LOW. 3. NEED TO FINISH FRAMING (01035) REFERENCE INSPECTION DONE 3/1/06 (REVISED PLANS, ETC.) 4. ACCESSIBLE SIGNAGE @ RESTROOMS TO BE ON WALL ADJACENT TO DOOR @ LATCH SIDE OF EACH DOOR (48"-60" TO C/L OF BRAILLE). 5. NEED TO LEAVE PERMIT ON SITE. 6. NEED SIGN @ MAIN EXIT DOOR (FRONT DOOR) "DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" - 1" MIN. LETTERS. |