Permit: T06CM00285

Parcel: 12409159A


Addresses:

1821 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORY'S ARE NOT PROPERLY IDENTIFIED
2. WIRING NOT COMPLETE IN DRIVE UP
3. IN CEILING - HAVE OPEN J-BOX, STRAP MC WITHIN 12" OF BOX AND USE LISTED STRAP FOR MC. ALSO, USE EQUIPMENT GROUND TO GROUND METAL BOXES.
4. PROVIDE EARTH GROUND TO ALARM PANEL
5. PROVIDE ACCESS TO ROOF.

PARTIAL INSPECTION