Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00285
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORY'S ARE NOT PROPERLY IDENTIFIED 2. WIRING NOT COMPLETE IN DRIVE UP 3. IN CEILING - HAVE OPEN J-BOX, STRAP MC WITHIN 12" OF BOX AND USE LISTED STRAP FOR MC. ALSO, USE EQUIPMENT GROUND TO GROUND METAL BOXES. 4. PROVIDE EARTH GROUND TO ALARM PANEL 5. PROVIDE ACCESS TO ROOF. PARTIAL INSPECTION |