Permit: T06CM00280

Parcel: 120073590


Addresses:

409 W AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM00280

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- WIRE SIZE FOR FEEDERS TO NEW J-BOX TO SMALL
- PLANS CALL FOR 3/0 TO J-BOX 2/0 TO SUB-PANEL "A"
- INSTALL BUSHINGS TO PROTECT CABLING AT TERMINATION
10/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. USE APPROVED WIRE NUTS OR SLEEVES TO PIGTAIL GROUNDS IN DEVICES.
2. SEE NOTE #3 LAST INSP.
08/24/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STAPLE ROMEX WITHIN 12" OF BOX OR TERMINATION
2. CANNOT RUN INDIVIDUAL CONDUCTOR OUTSIDE OF RACEWAY
3. INSTALLATION MUST MATCH APPROVED PLANS
08/14/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CODE COMPLIANCE QUESTIONS
03/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/13/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*