Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00280
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/27/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WIRE SIZE FOR FEEDERS TO NEW J-BOX TO SMALL - PLANS CALL FOR 3/0 TO J-BOX 2/0 TO SUB-PANEL "A" - INSTALL BUSHINGS TO PROTECT CABLING AT TERMINATION |
|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. USE APPROVED WIRE NUTS OR SLEEVES TO PIGTAIL GROUNDS IN DEVICES. 2. SEE NOTE #3 LAST INSP. |
|
| 08/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STAPLE ROMEX WITHIN 12" OF BOX OR TERMINATION 2. CANNOT RUN INDIVIDUAL CONDUCTOR OUTSIDE OF RACEWAY 3. INSTALLATION MUST MATCH APPROVED PLANS |
|
| 08/14/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CODE COMPLIANCE QUESTIONS |
|
| 03/13/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/13/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |