Permit: T06CM00280

Parcel: 120073590


Addresses:

409 W AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM00280

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/29/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLANS CALL OUT 2 1/2" CONDUIT/PROVIDE APPROVED PLANS
SERVICE NOT PER PLANS
03/27/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
24" MIN. DEPTH TOP OF CONDUIT TO FINISHED GRADE
PER 300.5 NEC.
03/13/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*