Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* PREVIOUS COMMENTS ADDRESSED ON NEW WORK |
|
| 02/14/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MC CABLE TO BE SUPPORTED TO STRUCTURE NOT CONDUIT 2) KEEP AWAY FROM COPPER LINES (MC) 3) SUPPORT J-BOXES TO STRUCTURE, IF BY WIRE TIE OFF-BOTH ENDS. SOME BOXES HAVE NO SUPPORT |