Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM00272
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/12/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OLD VDV CABLING TO BE AS PER 725.2 & 800.2 & 6 2. MAINTAIN WORKING CLEARANCE IN FRONT OF FAN COIL DISCONNECTS ALSO PLEASE LABEL. 3. BOXES IN CEILING NEED SUPPORT WIRES (SMOKE DETECTOR) 4. FILL UNUSED OPENINGS IN BOX. 5. BONDING DEVICES NEEDED AT CONCENTRIC/ECENTRIC OPENING IN BOXES 250.97 |