Permit: T06CM00272

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM00272

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/12/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OLD VDV CABLING TO BE AS PER 725.2 & 800.2 & 6
2. MAINTAIN WORKING CLEARANCE IN FRONT OF FAN COIL DISCONNECTS ALSO PLEASE LABEL.
3. BOXES IN CEILING NEED SUPPORT WIRES (SMOKE DETECTOR)
4. FILL UNUSED OPENINGS IN BOX.
5. BONDING DEVICES NEEDED AT CONCENTRIC/ECENTRIC OPENING IN BOXES 250.97