Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/12/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OLD VDV CABLING TO BE AS PER 725.2 & 800.2 & 6 2. MAINTAIN WORKING CLEARANCE IN FRONT OF FAN COIL DISCONNECTS ALSO PLEASE LABEL. 3. BOXES IN CEILING NEED SUPPORT WIRES (SMOKE DETECTOR) 4. FILL UNUSED OPENINGS IN BOX. 5. BONDING DEVICES NEEDED AT CONCENTRIC/ECENTRIC OPENING IN BOXES 250.97 |