Permit: T06CM00260

Parcel: 11105168A

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/14/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
THE ONLY ISSUES LEFT ARE
1. THE TEMPORARY WATER LINE AND
2. THE SEWER CONNECTION FROM REAR PROPERTIES

I SEE NO PROBLEM FOR TEMP C OF O
12/13/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. YARD WATER TO METER LOCATION OK TO COVER, TEMP WATER LINE OK WILL APPROVED YARD WATER AFTER INSP AT METER CONNECTION.
WHERE ARE YOUR PLANS?
WHY IS THE WATER OFF?
SITE SEWER NOT PER PLAN REVISION
12/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ORIGINAL APPROVED PLANS
2. WATER PIPING SHALL HAVE A MIN. OF 12" COVER
3. UNIT 2 TUB VALVE IS MISSING A COVERPLATE SCREW.
4. REMOVE COVER FOR VERIFICATION OF INTEGRAL SHUT OFF VALVES AS BOTH UNITS ARE CONTROLLED WITH ONE VALVE.
5. T&P DRAINS NOT TERMINATED
6. KIT. SINKS NOT WATER TIGHT TO COUNTERTOP AND ARE MISSING CLIPS IN FRONT. UNIT 2 WATER NOT ON SPRAY NOT COVERING HOLE.
11/16/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- WATER PIPING INSTALLED 2'-3' FROM STREET, AND IN RIGHT OF WAY.
- UTILITIES CANNOT RUN IN RIGHT OF WAY.
- PROVIDE APPROVED SITE UTILITY PLAN FOR WATER AND SEWER.
- PROVIDE JOINT SEWER AGREEMENT, CALL FOR SITE SEWER INSP.