Permit: T06CM00260

Parcel: 11105168A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/08/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/07/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BACK & FRONT BOX BY DOOR NOT GROUNDED, FIX BUSHING
2. GROUND ELECTRODE CONDUCTOR CUT ON #1
07/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER INTERIOR ELECTRICAL
NOTE:
1. GROUND EXTERIOR METAL BOXES
2. EXPOSE GROUNDING ELECTRODE CONDUCTOR
3. APPLY FOR OVERHEAD SERVICE WAIVER
07/14/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH ALL CORRECTIONS (#5, #7, #9)
06/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND ALL METAL BOXES
2. INSTALL NAIL PLATES
3. PROPERLY CONNECT ALL EQUIPMENT GROUNDS.
4. DISPOSAL, DISHWASHER AND REFER CANNOT SHARE SINGLE 20 AMP. CKT.
5. HOOD FAN NOT ALLOWED ON COUNTER CKT.
6. OUTLETS TO BE WITHIN 6' OF CLOSETS IN BEDROOMS
7. GROUNDING ELECTRODE CONDUCTOR NEEDS TO BE CONTINUOUS OR USE IRREVERSIBLE CRIMP -- SPLIT BOLT NOT ACCESSIBLE.
8. INSTALL ALL LIGHT BOXES/CANS?
9. NEED TO APPLY FOR WAIVER WITH CITY FOR OVERHEAD SERVICE AND INSTALL ADDRESS ON THEM.