Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BACK & FRONT BOX BY DOOR NOT GROUNDED, FIX BUSHING 2. GROUND ELECTRODE CONDUCTOR CUT ON #1 |
|
| 07/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER INTERIOR ELECTRICAL NOTE: 1. GROUND EXTERIOR METAL BOXES 2. EXPOSE GROUNDING ELECTRODE CONDUCTOR 3. APPLY FOR OVERHEAD SERVICE WAIVER |
|
| 07/14/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH ALL CORRECTIONS (#5, #7, #9) |
|
| 06/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND ALL METAL BOXES 2. INSTALL NAIL PLATES 3. PROPERLY CONNECT ALL EQUIPMENT GROUNDS. 4. DISPOSAL, DISHWASHER AND REFER CANNOT SHARE SINGLE 20 AMP. CKT. 5. HOOD FAN NOT ALLOWED ON COUNTER CKT. 6. OUTLETS TO BE WITHIN 6' OF CLOSETS IN BEDROOMS 7. GROUNDING ELECTRODE CONDUCTOR NEEDS TO BE CONTINUOUS OR USE IRREVERSIBLE CRIMP -- SPLIT BOLT NOT ACCESSIBLE. 8. INSTALL ALL LIGHT BOXES/CANS? 9. NEED TO APPLY FOR WAIVER WITH CITY FOR OVERHEAD SERVICE AND INSTALL ADDRESS ON THEM. |