Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GARAGE GFI NOT TRIPPING, REAR PORCH NOT TRIPPING (MISWIRED IN GARAGE GFI?) 2. ROOFTOP UNIT IS OVERFUSED - NEC 110.3 3. IDENTIFY ALL WHITES USED AS HOTS INCLUDING THREEWAYS - NEC 200 4. GROUND ALL METAL BOXES FOR ISLAND RECEPTACLES - NEC 314.4 5. FRONT EXTERIOR RECEPTACLE NOT GFI PROTECTED - NEC 210.8 6. PROVIDE PROPER SIZE CLAMP FOR GAS BOND & REMOVE PAINT - NEC 110.3 & 250.12 7. KITCHEN ISLAND RECESSED LIGHTS NOT WORKING. 8. SMOKE DETECTORS NOT WORKING/NOT ENERGIZED/NO POWER LIGHT. 9. APPEAR TO HAVE BURIED RECEPTACLE IN LAUNDRY? 10. HAVE SHORT CKT IN LAUNDRY ROOM SWITCHING CKT (LIGHTS) DO NOT CALL FOR REINSPECTION BEFORE ALL CORRECTIONS MADE OR A REINSPECTION FEE WILL BE CHARGED - HAVE ELECTRICIANS GO THROUGH UNITS BEFORE CALLING IN FOR ANY FINALS. |
|
| 12/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | INSTALL ADDRESS ON SERVICE BEFORE INSPECTION |