Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
08/08/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER PAUL |
|
07/25/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4/SD3 NOT COMPLIED WITH AT 2 X 12 BEAM 2) 4 X 12 BEAM WAYNED ON END BEARING ONLY 1 1/2" MUST BEAR 4" 3) 4 X 12 BEAM MUST BEAR ON DBL 2 X 4 POST. PRESENTLY POST IS CUT AND SPLICED 4) SHEARWALLS NOT NAILED 5) NO LADDER ACCESS TO ROOF 6) STOPPED INSPECTION |