Permit: T06CM00227

Parcel: 133233580


Addresses:

7685 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM00227

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/11/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE OVERFLOW SENSORS ON SECONDARY DRAINS
2. I.D DATA PLATES ON FAN COILS
3. I.D EQUIPMENT WITH UNIT NUMBER PERMANENTLY
4. PLANS REQUIRE COPPER CONDENSATE DRAINS
5. CONDENSORS NOT FUSED CORRECTLY
6. FAN COILS NOT FUSED CORRECTLY
7. PLANS REQUIRE INSULATION ON CONDENSATE DRAINS
8. AC FANS TO RUN CONTINUOUSLY WHILE THE BLDG IS OCCUPIED
9. AIR BALANCE OK
10. DUCT SMOKE DETECTORS OK