Permit: T06CM00227

Parcel: 133233580


Addresses:

7685 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00227

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH #12
2. INSTALL CEILING RECEPTACLES
06/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH ITEMS 1, 10 & 12

OK ROOF
06/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. APPROVED EXTENDER RINGS NEEDED FOR BOXES MORE THAN 1/4" BOX TO SURFACE - 314.20
2. CLEAN EXCESS TRASH & DIRT FROM FLOOR BOXES
3. SECURE FLOOR BOX COVER
4. USE TERMINAL ENDS WITH STRANDED CONDUCTORS
5. CORD CANNOT PASS THROUGH WALL 400.7 & 8
6. PANEL DIRECTORIES TO BE AS PER 408.4 -
NO ABBREVIATION
7. MAINTAIN WORKING & DEDICATED SPACE ABOUT DISCONNECTS - 110.26
8. CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
ALSO, BOND DISCONNECTS
9. CONTACTORS TO BE LISTED - NOT RECOGNIZED COMPONENTS
10. LIGHT FIXTURES NOT AS PER PLANS - BATHROOM
11. SECURE STAGER LIGHT FIXTURES TO STRUCTURE
12. FINISH VDV CABLING AS DISCUSSED ON ABOVE CEILING INSPECTION
13. WHERE IS ILLUMINATION FOR SES 110.26
14. BOX OVERFILLED
15. HALL EM LIGHT NOT WORKING
16. WHERE ARE BOTTOM EM LIGHTS?

ROOF:
1. BOND DISCONNECT ENCLOSURES
2. TIGHTEN LOOSE FITTINGS
3. FITTING TO BE LISTED FOR WET LOCATION
04/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*