Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T06CM00227
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
05/29/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* RECEIVED LETTER OF TORQUE |
|
05/28/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE PROVIDE A LETTER OF TORQUE 2. PROTECT CONDUCTOR AT PVC CONDUITS - 300.4 & 352.46 3. POST ADDRESS ON OUTSIDE OF SES 4. SECURE SES TO FLOOR 5. CABLE LASHING AS PER INSTRUCTIONS 6. FINISH PANELS |