Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM00227
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
06/23/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
06/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH VDV CABLING - CK ON FINAL OK TO TILE |
|
06/04/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH EXIT LIGHTS 2. SUPPORT VDV CABLING AS PER 725.24, 800.24, 300.11, 726 3. IF SUPPORTED MC WHIPS TO BE AS PER 300.11 4. FILL UNUSED CONDUIT OPENINGS 5. REMOVE ALL TILES IN ROOMS TO INSPECT - NO BORDERS OR ANY TILE UNTIL APPROVED |