Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* CALL IN 03035 & 03036 - 03037 PLANS REDLINES & REVISED ON SITE OK |
|
| 05/01/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 15 PSI TEST FROM METER LOCATION TO VALVES ON ROOFTOP AND PIPED THRU DISTRIBUTION HEADER AT KITCHEN. 1. NEED TO VERIFY GAS TO APPLIANCES WHEN INSTALLED. CLOSET FLANGES OK OVERHEAD OK EXCEPT IN WATER HEATER CLOSET. NEED TO SEE VENT CONNECTION OVERHEAD. |
|
| 04/27/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* FROM METER THRU BUILDING TO CAPS ON ROOF STUBS AND 2" CAP AT KITCHEN WALL 15 PSI TEST PARTIAL. 1. RETEST SYSTEM ON COMPLETION OF KITCHEN GAS PIPING. 2. PROVIDE REVISED APPROVED PLAN OF ALL RELINES ON THIS PROJECT AND REDLINE DRAWING ON SITE AT FUTURE DATE. |