Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM00219

Parcel: 136088090


Addresses:

9620 E 22ND ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM00219

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/12/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NEED AIR BALANCE REPORT
OK FOR TEMP C OF O
09/11/2006 MECHANICAL - FINAL Denied PERMANENTLY IDENTIFY EQUIPMENT ON ROOF.
PROVIDE FRESH AIR INTAKES
2 UNITS NOT PROPERLY FUSED
NEED TO TEST DUCT SMOKE DETECTORS
PROVIDE A COPY OF CERTIFIED AIR BALANCE REPORT.