Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EXIT & EM LIGHTING 1. FINISH A/C DISCONNECTS |
|
| 09/12/2006 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C OF O FOR STOCKING 1. WILL REVIEW EXIT SIGNAGE EM LIGHTING AT FINAL 2. USE GROUNDING BUSHINGS AT 480V AC UNIT DISCONNECTS 3. FINISH ALL LIGHTING, EXIT AND NIGHT LIGHTING 4. AC WIRING -- 277/480V AT DISCONNECTS --NEED BOND BUSHINGS WHERE GOING THRU CONCENTRIC KO'S |
|
| 09/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/31/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TEMP POWER FOR TEST PER R.H 8/29 CLEARED TEC CLEARED BY R. HOLLANDER |