Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CONSTRUCTION POWER
Permit Number - T06CM00191
Inspection Description - ELECTRIC - CONSTRUCTION POWER
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 01/17/2007 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL CORRECT SIZE FUSES FOR FEEDERS - NEC 310 2. HAVE OVER 360 DEG. OF BENDS IN FEEDER RACEWAY - NEC 358.26 3. IF FEEDER CONDUCTORS ARE INCREASED, SO MUST EQUIPMENT GROUND SIZE - NEC 250.122 B HAVE GEAR OPEN SO I CAN INSPECT FEEDER TERMINATIONS 4. EMT NOT PROPERLY SUPPORTED - NEC 358.30 |