Permit: T06CM00191

Parcel: 10819224A


Addresses:

811 E WETMORE RD 02


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T06CM00191

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
01/17/2007 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL CORRECT SIZE FUSES FOR FEEDERS - NEC 310
2. HAVE OVER 360 DEG. OF BENDS IN FEEDER RACEWAY -
NEC 358.26
3. IF FEEDER CONDUCTORS ARE INCREASED, SO MUST EQUIPMENT GROUND SIZE - NEC 250.122 B
HAVE GEAR OPEN SO I CAN INSPECT FEEDER TERMINATIONS
4. EMT NOT PROPERLY SUPPORTED - NEC 358.30