Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00191
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 08/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BRACE RECEPTACLE BOXES ON STEEL STUDS TO PREVENT BOX ROLL. 2. PROVIDE PROPER DEPTH MUD RING FOR FINISHED SURFACE 3. CHECK FRONT AREA RECEPTACLE? OK TO COVER ELECTRICAL AFTER CORRECTIONS IN WALLS (SOUTH AREA ONLY). |