Permit: T06CM00187

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/16/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL. LAST INSPECTOR TO CLEAR
06/14/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #4 PREVIOUS INSPECTION.
06/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH PREVIOUS ITEMS.
06/09/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BONDING FOR MEYERS HUBS TO USE MANUFACTURERS LISTED PARTS. SHEET METAL SCREWS NOT ALLOWED 110.5 & 250.8
2. PROTECT OBJECTIONABLE CURRENT 250.6 - REMOVE GROUNDING CONDUCTOR THRU RACEWAY METER TO DISCONNECT.
3. NEED REJECTION PINS
4. ANGLE PULLS TO BE AS PER 314.28 (A)(2)
OK UNDERGROUND CONDUITS.