| 06/16/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL. LAST INSPECTOR TO CLEAR |
|
| 06/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #4 PREVIOUS INSPECTION. |
|
| 06/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS. |
|
| 06/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BONDING FOR MEYERS HUBS TO USE MANUFACTURERS LISTED PARTS. SHEET METAL SCREWS NOT ALLOWED 110.5 & 250.8 2. PROTECT OBJECTIONABLE CURRENT 250.6 - REMOVE GROUNDING CONDUCTOR THRU RACEWAY METER TO DISCONNECT. 3. NEED REJECTION PINS 4. ANGLE PULLS TO BE AS PER 314.28 (A)(2) OK UNDERGROUND CONDUITS. |