Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM00185
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK CEILING TILES |
|
12/21/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DUCT NOT SECURED TO START COLLAR DO NOT USE DUCT TAPE TO SECURE INSULATION OK FOR PARTIAL CEILING TILES DINING AREA |
|
12/13/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ITEMS #3 & #5 FROM PREVIOUS INSPECTION NOT COMPLETED I CAN CHECK ITEM #3 ON FINAL. OK TILES IN KITCHEN ONLY. |
|
12/07/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FIRE WRAP OK 2. SUPPLY DUCT MISSING TO OFFICE. 3. PROVIDE A TRAP AT END OF WALK-IN CONDENSATE DRAIN. 4. REMOVE ALL ABANDONED DUCTING 5. SECURE DUCT INSULATION AT COLLARS 6. BLANK OFF UNUSED SUPPLY OPENINGS IN TRUNK LINE. |
|
08/15/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - CHECKED WELDS ON GREASE DUCT. - OK TO FIRE WRAP - BE SURE TO WRAP UPPER SECTION PRIOR TO INSTALLING DUCT. |
|
06/05/2006 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |