Permit: T06CM00185

Parcel: 13348128D

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM00185

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) OK CEILING TILES
12/21/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
DUCT NOT SECURED TO START COLLAR
DO NOT USE DUCT TAPE TO SECURE INSULATION
OK FOR PARTIAL CEILING TILES DINING AREA
12/13/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
ITEMS #3 & #5 FROM PREVIOUS INSPECTION NOT COMPLETED
I CAN CHECK ITEM #3 ON FINAL.
OK TILES IN KITCHEN ONLY.
12/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FIRE WRAP OK
2. SUPPLY DUCT MISSING TO OFFICE.
3. PROVIDE A TRAP AT END OF WALK-IN CONDENSATE DRAIN.
4. REMOVE ALL ABANDONED DUCTING
5. SECURE DUCT INSULATION AT COLLARS
6. BLANK OFF UNUSED SUPPLY OPENINGS IN TRUNK LINE.
08/15/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
- CHECKED WELDS ON GREASE DUCT.
- OK TO FIRE WRAP
- BE SURE TO WRAP UPPER SECTION PRIOR TO INSTALLING DUCT.
06/05/2006 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*