Permit: T06CM00185

Parcel: 13348128D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00185

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GFI RECEPTACLE AT OUTSIDE RESTROOM WILL NOT RESET
2. INSTALL SERVICE RECEPTACLE FOR LOW ROOF REFRIGERATION EQUIPMENT
3. MARK CIRCUITS AT PANEL FOR BEER COOLER.
INSTALL 2 POLE BREAKER FOR THESE CIRCUITS.
09/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY VICTOR
06/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BATHROOM GFI RECEPT HAS NO POWER/WILL NOT RESET
2. COMPLETE INSTALLATION OF LOW VOLTAGE LIGHTING. HAVE INSTALLATION INSTRUCTIONS ON SITE.
3. NEED TO INSTALL RECEPT FOR CAPPUCCINO MACHINE
4. CHECK LOAD ON DIMMERS MAY BE EXCEEDING RATING OF DIMMERS
5. INSTALL GFI RECEPT ON KITCHEN RECEPT OR INSTALL SINGLE DEDICATED RECEPT OF EQUIPMENT TO BE SERVED.
6. REPLACE DAMAGED CORD ON MEAT SLICER
7. PROPERLY INSTALL SWITCH IN OFFICE
8. SPOT COOLER IN WALK-INS NEED DISCONNECTS
9. ENSURE RACEWAYS SEALED FEEDING WALK-IN COOLER/FREEZER
10. BEER COOLER NOT WIRED
11. STRAP SEAL TIGHT ON ROOF
12. DISCONNECT OLD WIRING ON ROOF
13. RUN LOW VOLTAGE LIGHTING FOR OUTSIDE LIGHTING CLOSER TO BUILDING SURFACE.
03/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE INSTALLATION OF THE FLUORESCENT STRIP LIGHT INSTALLED ON THE INSIDE EDGE OF THE INSIDE CANOPYS PRESENTS SEVERAL PROBLEMS.
1. THE LISTING OF THE FIXTURE HAS TO BE APPROVED FOR THE METHOD IT IS BEING USED -- NO LISTING SHOWN THIS IS REQUIRED PR NEC 2002 110.2,3
2. THE WIRING METHOD USED -- CORD IS NOT ALLOWED FOR PERMANENT WIRING METHODS AS PER NEC 400.8 USES NOT PERMITTED.