Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00185
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GFI RECEPTACLE AT OUTSIDE RESTROOM WILL NOT RESET 2. INSTALL SERVICE RECEPTACLE FOR LOW ROOF REFRIGERATION EQUIPMENT 3. MARK CIRCUITS AT PANEL FOR BEER COOLER. INSTALL 2 POLE BREAKER FOR THESE CIRCUITS. |
|
09/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY VICTOR |
|
06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BATHROOM GFI RECEPT HAS NO POWER/WILL NOT RESET 2. COMPLETE INSTALLATION OF LOW VOLTAGE LIGHTING. HAVE INSTALLATION INSTRUCTIONS ON SITE. 3. NEED TO INSTALL RECEPT FOR CAPPUCCINO MACHINE 4. CHECK LOAD ON DIMMERS MAY BE EXCEEDING RATING OF DIMMERS 5. INSTALL GFI RECEPT ON KITCHEN RECEPT OR INSTALL SINGLE DEDICATED RECEPT OF EQUIPMENT TO BE SERVED. 6. REPLACE DAMAGED CORD ON MEAT SLICER 7. PROPERLY INSTALL SWITCH IN OFFICE 8. SPOT COOLER IN WALK-INS NEED DISCONNECTS 9. ENSURE RACEWAYS SEALED FEEDING WALK-IN COOLER/FREEZER 10. BEER COOLER NOT WIRED 11. STRAP SEAL TIGHT ON ROOF 12. DISCONNECT OLD WIRING ON ROOF 13. RUN LOW VOLTAGE LIGHTING FOR OUTSIDE LIGHTING CLOSER TO BUILDING SURFACE. |
|
03/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE INSTALLATION OF THE FLUORESCENT STRIP LIGHT INSTALLED ON THE INSIDE EDGE OF THE INSIDE CANOPYS PRESENTS SEVERAL PROBLEMS. 1. THE LISTING OF THE FIXTURE HAS TO BE APPROVED FOR THE METHOD IT IS BEING USED -- NO LISTING SHOWN THIS IS REQUIRED PR NEC 2002 110.2,3 2. THE WIRING METHOD USED -- CORD IS NOT ALLOWED FOR PERMANENT WIRING METHODS AS PER NEC 400.8 USES NOT PERMITTED. |