Permit: T06CM00185

Parcel: 13348128D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM00185

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABLING 725.6 & 800.6
2. SUPPORT M/C CABLE AND DO NOT BUNDLE 300.11
3. FIXTURE TO BE ATTACHED TO GRID 410.16

OK BATHROOM WALLS
10/19/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
7:46 AM DOOR LOCKED
NO MESSAGE LEFT
CALL ME IF YOU HAVE ANY QUESTIONS 954-0161
07/06/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*