Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 04/13/2006 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 04/12/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW EXTERIOR WALL FOOTING SHOULD BE 1'4" IN WIDTH PER DETAIL 103 ON SHEET S-1 2. #4 BOWERS SHOULD EXTEND 4' INTO SLAB PER DETAILS 103 & 104 ON SHEET S-1 3. FOOTING FOR NEW FUR IN WALL SHOULD REFLECT DETAIL 105 ON SHEET S-1. #5 DOWERS SHOULD BE EPOXIED INTO EXISTING FOOTING NOT THE STEM WALL. ADDITIONAL #4 DOWERS SHOULD ALSO BE PLACED PER DETAIL 105. |