Permit: T06CM00185

Parcel: 13348128D

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T06CM00185

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
04/13/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
04/12/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEW EXTERIOR WALL FOOTING SHOULD BE 1'4" IN WIDTH PER DETAIL 103 ON SHEET S-1
2. #4 BOWERS SHOULD EXTEND 4' INTO SLAB PER DETAILS 103 & 104 ON SHEET S-1
3. FOOTING FOR NEW FUR IN WALL SHOULD REFLECT
DETAIL 105 ON SHEET S-1. #5 DOWERS SHOULD BE EPOXIED INTO EXISTING FOOTING NOT THE STEM WALL. ADDITIONAL #4 DOWERS SHOULD ALSO BE PLACED PER DETAIL 105.