Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/08/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 12" SUPPLY DUCT CANNOT BE RESTRICTED MORE THAN 1/3 PRESENTLY ? TO 5". MUST HAVE MINIMUM 8" WIDTH 2) PEX NOT ALLOWED WITHIN 12" OF RECESSED LIGHT HALL AND KITCHEN 3) NO DWV TEST 4) CONDENSATE REVERSE PITCH 5) PERM CAP ABANDONED DWV 6) MAX LAV DIAMETER 1 1/2" DIRTY ARM 7) SEAL FLOOR PENETRATIONS 8) CLIP TRUSS FRONT BEDROOM 9) CHASE FIRE STOP REQUIRES 2 LAYERS 1/2" OSB ? |