Permit: T06CM00152

Parcel: 140550560

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/13/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/12/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/08/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 12" SUPPLY DUCT CANNOT BE RESTRICTED MORE THAN 1/3 PRESENTLY ? TO 5". MUST HAVE MINIMUM 8" WIDTH
2) PEX NOT ALLOWED WITHIN 12" OF RECESSED LIGHT HALL AND KITCHEN
3) NO DWV TEST
4) CONDENSATE REVERSE PITCH
5) PERM CAP ABANDONED DWV
6) MAX LAV DIAMETER 1 1/2" DIRTY ARM
7) SEAL FLOOR PENETRATIONS
8) CLIP TRUSS FRONT BEDROOM
9) CHASE FIRE STOP REQUIRES 2 LAYERS 1/2" OSB ?