Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM00123
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2006 | ELECTRIC - ABOVE CEILING | Approved | ||
01/27/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. FINISH VDC CABELING 2. PLANS WITH PANEL SCHEDULE AND LOAD NOT OBVIOUS SUBMIT REVISED PLANS AS PER NOT ABOVE. 3. FULLY TERMINATE CONDUCTORS UNDER SCREW TERMINALS (ALSO 3/4 OF A TURN CLOCKWISE) 4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 5. PLEASE CLEAN EXCESS PAINT AND DEBRIS FROM DEVICE TERMINALS |
|
01/23/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*FINISH ABOVE CEILING ITEMS.CHECK ON FINAL | |
01/18/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*PROTECT CABLES AND FLEX AT STUDS THRU IS NOT AN APPROVED WIRING METHOD SUPPORT M/C CABLE ? OFF OF GRID AND??? APPROVED SUPPORTS. RIDGIDY SUPPORT BOXES ON STUDS VDB CABLEING TO BE AS PER 725.2 & 6, 760.2 &6, 800.2 & 6 PLEASE CORRECT SUITE #. THIS IS 207 |