Permit: T06CM00123

Parcel: 12701004C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM00123

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2006 ELECTRIC - ABOVE CEILING Approved
01/27/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. FINISH VDC CABELING
2. PLANS WITH PANEL SCHEDULE AND LOAD NOT OBVIOUS SUBMIT REVISED PLANS AS PER NOT ABOVE.
3. FULLY TERMINATE CONDUCTORS UNDER SCREW TERMINALS (ALSO 3/4 OF A TURN CLOCKWISE)
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING
5. PLEASE CLEAN EXCESS PAINT AND DEBRIS FROM DEVICE TERMINALS
01/23/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*FINISH ABOVE CEILING ITEMS.CHECK ON FINAL
01/18/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*PROTECT CABLES AND FLEX AT STUDS
THRU IS NOT AN APPROVED WIRING METHOD
SUPPORT M/C CABLE ? OFF OF GRID AND??? APPROVED SUPPORTS.
RIDGIDY SUPPORT BOXES ON STUDS
VDB CABLEING TO BE AS PER 725.2 & 6, 760.2 &6, 800.2 & 6
PLEASE CORRECT SUITE #. THIS IS 207