Permit: T06CM00115

Parcel: 107132130

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ROOFTOP GFI FOR WEST UNIT SHOWS OPEN NEUTRAL.
2. STILL HAVE WRONG SIZE CONNECTOR FOR COOLER CORDS.
3. PANEL DIRECTORY'S STILL NOT CORRECTLY IDENTIFIED.
4. MAX BREAKER TO FURNACE 30 AMP.
5. PROTECT ATTIC WIRING.
6. STILL HAVE UNIDENTIFIED WHITES USED AS HOTS @ HWT
7. PROVIDE EXPLANATION OF ALTERED SUB-PANEL.
8. STILL HAVE SEVERAL LOOSE DEVICES/BOXES
9. WIRING TO WEST ROOF GFI TO BE PROPERLY SECURED AND SUPPORTED.

REINSPECTION FEE IF NOT CORRECT NEXT TIME.
10/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ON ROOF
1. TERMINATE ALL EQUIPMENT GROUNDS IN COOLER J-BOXES
NEC 250.4
2. USE PROPER SIZE CONNECTOR FOR CABLES ENTERING COOLERS -- NEC 110.3
3. NEED 120V SERVICE RECEPTACLE FOR WEST UNIT --
NEC 210.63
4. WHITE CONDUCTOR USED AS HOT NEEDS TO BE PROPERLY IDENTIFIED -- NEC 200.7
5. EXTERIOR SWITCH COVERS TO BE WEATHERPROOF AND INSTALL FIXTURE GLOBES.
6. TIGHTEN ALL LOOSE DEVICES.
7. INSTALL ALL DEVICE COVERS.
8. ALL SWITCHES TO BE GROUNDED
9. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4
10. HOOD NEEDS ROMEX CONNECTOR
11. NEED PROPER CONNECTOR FOR FURNACE CKT. AND STAPLE PROPERLY.
12. ALL WIRING WITHIN 6' OF ATTIC ACCESS TO BE PROTECTED NEC 334.23
13. MAXIMUM OVERCURRENT PROTECTION TO FURNACE IS 30 AMPS
14. WEST UNIT PANEL ALTERED
09/11/2006 ELECTRIC - FINAL Not ready for Inspection CALL FOR FINAL WHEN ENERGIZED