Permit: T06CM00111

Parcel: 141094900

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM00111

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2006 FRAMING Approved
07/19/2006 FRAMING Partial Approval IVRS - Inspection :*
1) HAVE TRUSS REPAIR APPROVED FOR THIS ADDRESS. REPAIR IS PER DRAWING
2) OK TO INSULATE AND DRYWALL
07/18/2006 FRAMING Cancelled IVRS - RI canceled
07/10/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A05 DRAG TRUSS DAMAGED. PROVIDE CITY OF TUCSON APPROVED TRUSS REPAIR DOCUMENT
2) GARAGE SHEARWALL REQUIRES 5 ANCHOR BOLTS
3) 5/D3 NOT COMPLIED WITH AT SHEARWALL
4) SHEARWALLS REQUIRE ANCHOR BOLTS