Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM00105
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
08/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE STEM WALL REPAIRS COVERED WITHOUT CITY OF TUCSON INSPECTION. PROVIDE PROOF OF CITY INSPECTION OR PROVIDE PACHOMETER TESTING BY CERTIFIED COMPANY 2) ENGINEERING MUST BE APPROVED BY CITY OF TUCSON |
|
05/24/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) OK TO LATHE HOLDOWNS AT GARAGE NEED ENGINEERING FOR RETRO FIT HOLDOWNS. CONCRETE UNDER BOTTOM PLATE AT HOLDOWNS CHANGED |
|
05/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAP GABLE END ABOVE GARAGE 2ND FLOOR 2) BANG PLATE 3) STRAP TOP PLATE AT BREAKS 4) LEDGER NOT NAILED CORRECTLY BACK PORCH 5) SHEAR ON BACK OF HOUSE NOT NAILED TO PLAN 6) SHEAR ON ROOF NEED TO BE NAILED 8D'S |