Permit: T06CM00099

Parcel: 120086920


Addresses:

4802 S 12TH AV #100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/16/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/10/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/09/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUND RODS NOT INSTALLED PROPERLY -- DO NOT BEND,
8' IN GROUND, 8' MIN. APART, CODE ALLOWS A 45 DEGREE ANGLE MAX.
2. OK INSIDE ROUGH.