Permit: T06CM00094

Parcel: 140261280

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM00094

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2006 FRAMING Approved IVRS - Inspection :*
05/04/2006 FRAMING Partial Approval IVRS - Inspection :*
1) PROVIE RETRO FOR SLAB AT LAUNDRY
05/02/2006 FRAMING Cancelled IVRS - RI canceled
04/28/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS INSPECTION
2) REFEE
04/14/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCK COMBUSTION VENTS
2) LEAK AT DOWNSTAIR BATH
3) PROVIDE CLEARANCE FLU PIPE/FHA STRAP 2ND FLOOR
4) INSTALL VENT AT MASTER BATH
04/13/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) B-VENT NOT VERTICALLY SLOPED ENOUGH
2) MISSING HOLDOWN UNDER STAIRS
3) BANG PLATES THRU-OUT
4) SHEARWALL IN GARAGE NOT NAILED AT 3"
5) PLUMBING IN BOTTOM FLOOR NOT SUPPORTED
6) STOPPED INSPECTION