Permit: T06CM00092

Parcel: 106050210


Addresses:

446 W PELAAR DR #01


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM00092

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/19/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE SCREENS IN ALL T-TOPS ON ROOF EXCEPT FOR THE DRYER VENT. PROVIDE ROOF JACKS AT CONDENSATE DRAIN PENETRATION THRU ROOF.
DO NOT USE WHITE WIRE TO POWER A/C UNITS.
TAPE ENDS WITH BLACK TAPE.
MARK THE UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY AS PER 240V RATING.
PROVIDE FILTERS IN FRESH AIR INTAKES.