Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM00092
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2006 | PLUMBING - INTERMEDIATE | Approved | STILL APPROVED | |
07/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO SEE CLOSET FLANGES OK TO COVER ALL AREAS |
|
07/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO CHANGE FROM LAST INSPECTION CONTINUED "NOT READY'S" MAY RESULT IN A REINSPECTION FEE |
|
07/11/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. NO MORE THAN FOUR FEET BETWEEN HANGERS. 2. FILL TUBS ALL THE WAY UP. 3. INSPECTION STOPPED. |
|
07/10/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/05/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE POST YOUR ADDRESS 2) SUPPORT VERTICAL PIPE 3) SUPPORT OVERHEAD PIPE 4) WATER TEST OKAY 5) FILL TUBS ALL THE WAY UP 6) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 7) MISSION SHOWER 8) REVERT BELOW 42" TO BE SWEEPS |