Permit: T06CM00092

Parcel: 106050210


Addresses:

446 W PELAAR DR #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00092

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MICRO HOOD IS MOUNTED TO CLOSE TO RANGE --
SEE INSTALLATION MANUAL NEC 110.3
2. PANEL DIRECTORY IS INCORRECTLY IDENTIFIED - NEC 408.4
3. MAXIMUM 4' CORD ON DISHWASHER - NEC 422.16 B2
4. IDENTIFY WHITE CONDUCTOR USED AS HOT @ DISCONNECTS -- NEC 310.12
5. AC DISCONNECT OVER FUSED, AND IDENTIFY IF HEATER KIT IS INSTALLED.
6. NEED ROOFTOP SERVICE RECEPTACLE FOR EACH UNIT UNLESS SUPPLIED BY "HOUSE" PANEL -- 210.63
7. INSPECTION/PERMIT IS FOR UNIT ONE ONLY REVISE PERMIT TO SHOW UNIT #1 AND #2 FOR THIS ADDRESS.
8. NEED PROPER CONNECTOR FOR DISHWASHER CORD --
NEC 400