Permit: T06CM00064

Parcel: 136087660


Addresses:

9560 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06CM00064

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
GAS CARD ON PIPE AT METER
PROVIDE SADDLES UNDER PIPING IN HANGERS WITH INSULATION.
10/30/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
SYSTEM TO HOLD WITH NO LOSS OF PRESSURE.
RECEIVED LETTER FROM ENGINEER GIVING OK FOR SCREW
PIPE AT 2" DROP FOR KITCHEN EQUIP.
10/27/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
10/11/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
FROM METER OVERHEAD TO WATER HEATER, ROOF TOP UNITS DOWN TO 2" CAP AT COOKING BATTERY WALL 15 PSI TEST PARTIAL SEE NOTE 1 FROM 10/9/06 AND RETEST WHEN ANSUL VALVE & COMPLETION OF PIPING.
10/09/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE SEALED LETTER FROM ENGINEER GIVING OK PER NON-WELDED PIPIE AT COOKING BATTERY DROP PER PLAN
TEST IS NOT HOLDING PRESSURE VERIFY - NO LEAKAGE!
09/26/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PIPING PER PLAN 2" IN WALL TO BE WELDED PER PLAN.
2. TEST SHALL HOLD WITH NO PRESSURE LOSS.
09/20/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*