Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T06CM00064
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* GAS CARD ON PIPE AT METER PROVIDE SADDLES UNDER PIPING IN HANGERS WITH INSULATION. |
|
10/30/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* SYSTEM TO HOLD WITH NO LOSS OF PRESSURE. RECEIVED LETTER FROM ENGINEER GIVING OK FOR SCREW PIPE AT 2" DROP FOR KITCHEN EQUIP. |
|
10/27/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
10/11/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* FROM METER OVERHEAD TO WATER HEATER, ROOF TOP UNITS DOWN TO 2" CAP AT COOKING BATTERY WALL 15 PSI TEST PARTIAL SEE NOTE 1 FROM 10/9/06 AND RETEST WHEN ANSUL VALVE & COMPLETION OF PIPING. |
|
10/09/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE SEALED LETTER FROM ENGINEER GIVING OK PER NON-WELDED PIPIE AT COOKING BATTERY DROP PER PLAN TEST IS NOT HOLDING PRESSURE VERIFY - NO LEAKAGE! |
|
09/26/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PIPING PER PLAN 2" IN WALL TO BE WELDED PER PLAN. 2. TEST SHALL HOLD WITH NO PRESSURE LOSS. |
|
09/20/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |