Permit: T06CM00064

Parcel: 136087660


Addresses:

9560 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM00064

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/02/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) 03005 & 03040 REQUIRE CITY APPROVED REVISED PLAN FOR 7/12/06 INSPECTION
2) 03090 1" LANDSCAPING WATER SUPPLY SHALL BE COPPER INSIDE BLDG TO EXTERIOR WITH CORRECT LANDSCAPING BACKFLOW PROTECTION WITH CERTIFICATION
3) WATER HEATER T & P TO GRAVITY DRAIN TO DAYLIGHT OR APPROVED INDIRECT RECEPTOR
4) SUPPORT EXPANSION TANK
5) COMPLETE INSULATION ON WATER PIPING PER PLAN
6) PROVIDE FITTINF FOR TEE-CONNECTION FOR WATER SUPPLY TO ? FUSION
7) PROVIDE CORRECT FITTINGS FOR WATER SUPPLY TO ? WITH CORRECT BACKFLOW PROTECTION AND CERTIFICATIONS
8) HAVE ALL EQUIPMENT INSTALLED AND CORRECTLY HOOKED UP
09/20/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
07/18/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PIPE WRAPS OK
WATER - 2" T/K LOOPED IN FOR SERVICE UP & OUT APP. 3'
07/13/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" GREASE WASTE FROM INTERCEPTOR THRU BUILDING WATER TEST OK UNDERGROUND.
4" SANITARY DRAINAGE FROM 5' EXTERIOR WEST WALL THRU BUILDING UNDERGROUND WATER TEST OK PER REDLINE ON SITE.
1. NEED REVISED CITY APPROVED PLAN & REDLINE AT LATER DATE OF SANITARY & GREASE WASTE INTERCEPTOR LOCATION & DISCHARGE WITH TEST OF CONTINUATION OF BOTH.
07/12/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
07/12/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIPING TO BE INSTALLED PER APPROVED PLAN.
PROVIDE REVISED APPROVED PLAN OF SANITARY DRAINAGE &
ORIENTATION OF INTERCEPTOR.
NOTE: GREASE WASTE TRAP ARMS TO HAVE CORRECT FALL. PROVIDE CORRECT DRAINAGE FITTING FOR DRAIN ARMS ON 2" FLOOR DRAINS (SANTEES REQUIRED) 4" DRAIN ARM FOR 4" FLOOR SINK TO HAVE VENT IN CORRECT LOCATION OF DRAIN ARM.