Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM00064
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
11/02/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) 03005 & 03040 REQUIRE CITY APPROVED REVISED PLAN FOR 7/12/06 INSPECTION 2) 03090 1" LANDSCAPING WATER SUPPLY SHALL BE COPPER INSIDE BLDG TO EXTERIOR WITH CORRECT LANDSCAPING BACKFLOW PROTECTION WITH CERTIFICATION 3) WATER HEATER T & P TO GRAVITY DRAIN TO DAYLIGHT OR APPROVED INDIRECT RECEPTOR 4) SUPPORT EXPANSION TANK 5) COMPLETE INSULATION ON WATER PIPING PER PLAN 6) PROVIDE FITTINF FOR TEE-CONNECTION FOR WATER SUPPLY TO ? FUSION 7) PROVIDE CORRECT FITTINGS FOR WATER SUPPLY TO ? WITH CORRECT BACKFLOW PROTECTION AND CERTIFICATIONS 8) HAVE ALL EQUIPMENT INSTALLED AND CORRECTLY HOOKED UP |
|
09/20/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
07/18/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* PIPE WRAPS OK WATER - 2" T/K LOOPED IN FOR SERVICE UP & OUT APP. 3' |
|
07/13/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" GREASE WASTE FROM INTERCEPTOR THRU BUILDING WATER TEST OK UNDERGROUND. 4" SANITARY DRAINAGE FROM 5' EXTERIOR WEST WALL THRU BUILDING UNDERGROUND WATER TEST OK PER REDLINE ON SITE. 1. NEED REVISED CITY APPROVED PLAN & REDLINE AT LATER DATE OF SANITARY & GREASE WASTE INTERCEPTOR LOCATION & DISCHARGE WITH TEST OF CONTINUATION OF BOTH. |
|
07/12/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
07/12/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PIPING TO BE INSTALLED PER APPROVED PLAN. PROVIDE REVISED APPROVED PLAN OF SANITARY DRAINAGE & ORIENTATION OF INTERCEPTOR. NOTE: GREASE WASTE TRAP ARMS TO HAVE CORRECT FALL. PROVIDE CORRECT DRAINAGE FITTING FOR DRAIN ARMS ON 2" FLOOR DRAINS (SANTEES REQUIRED) 4" DRAIN ARM FOR 4" FLOOR SINK TO HAVE VENT IN CORRECT LOCATION OF DRAIN ARM. |