Permit: T06CM00038

Parcel: 120085130


Addresses:

4833 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
08/16/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
08/11/2006 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1. GROUND TO WATER PIPNG MUST BE TO BLD WATER PIPING NOT IRRIGATION.
2. REMOVE BOND LINK BETWEEN NEUTRAL & GROUND BAR INSIDE PANEL.
3. FOR CONST. POWER, INSTALL GFI RECEPTS TO BE USED FOR TOOLS.