Permit: T06CM00023

Parcel: 13316013B


Addresses:

6500 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/31/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
03/28/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. TERMINATE ALL STRANDS AT BREAKERS - LP-12
2. CLEAN SURFACE UNDER GROUND LUG TO COLUMN
3. TIGHTEN LOOSE FITTING
4. USE APPROVED FITTIG AT LB
5. USE NON-COMBUSTIBLE PRODUCT AT SEAL TO WALK IN BOX
6. GUTTER BOND TO BE SIZE PER LARGEST OUTER CURRENT DEVICE.
7. PLEASE VERIFY LISTING & LABEL FOR WALK IN BOX
8. DISCONNECTING MEANS NOT TO BE ON A REMOVABLE PANEL 440.14
9. PROTECT CONDUCTORS FROM SHARP METAL EDGES.
10. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8