Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TERMINATE ALL STRANDS AT BREAKERS - LP-12 2. CLEAN SURFACE UNDER GROUND LUG TO COLUMN 3. TIGHTEN LOOSE FITTING 4. USE APPROVED FITTIG AT LB 5. USE NON-COMBUSTIBLE PRODUCT AT SEAL TO WALK IN BOX 6. GUTTER BOND TO BE SIZE PER LARGEST OUTER CURRENT DEVICE. 7. PLEASE VERIFY LISTING & LABEL FOR WALK IN BOX 8. DISCONNECTING MEANS NOT TO BE ON A REMOVABLE PANEL 440.14 9. PROTECT CONDUCTORS FROM SHARP METAL EDGES. 10. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 |