Permit: T06CM00018

Parcel: 107031480

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
01/12/2006 FIRE SPKLR - FINAL Approved
01/05/2006 FIRE SPKLR - FINAL Denied 1. Replace painted fire sprinkler in restroom.
2. Remove pendent sprinkler in Riser Room or replace ceiling.
3. Remove canopy structure in display room or add fire sprinkler protection beneath it.
Fire sprinkler work must be done by a licensed fire sprinkler contractor.