Permit: T06BU02722

Parcel: 131071010


Addresses:

6202 E 25TH ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/13/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
12/07/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
CLIPS OKAY
EXTERIOR S/R NAILING OKAY
12/06/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EAST WALL ON SOUTH END REQ'S 48" BRACED WALL PANEL PER PLAN
2. STHD8 @ FRONT REQUIRE 10D COMMON MIN. NAIL SIZE
3. PROVIDE REVISED PLAN WITH CITY APPROVAL AS PREVIOUSLY REQUESTED.